Specification | 1Æ Surge Diverter | ||
Power ratings:
AC voltage ratings (Optional) Operating Time |
Ph ~ N and Ph ~ E
Frequency Power System Nano seconds |
110, 240, 275 and 415 (T*)
50 or 60 Hz TT, TN-S, TN-C, TN-C-S(MEN) <10ns |
![]() |
Surge Diverter Ratings:
Surge Waveform KA (8/20ms) |
SDM-080K-M-RR/T
SDM-100K-M-RR/T SDM-140K-M-RR/T SDM-160K-M-RR/T |
080KA
100KA 140KA 160KA |
|
Modes of Protection
The aggregate surge material may be distributed over three optional mode, Line ~ Neutral (Differential Mode) Line ~ Earth (Common Mode) and Neutral ~ Earth (Common Mode) (*T-Thermal Cut Off) |
Mode identification
SDM-xxxK-P-RR/T SDMne-xxxK-P-RR/T SDM2-xxxK-P-RR/T SDM3-xxxK-P-RR/T |
Aggregate Distribution
Line ~ Neutral = 50% Line ~ Earth = 50% Neutral ~ Earth = 100% Line~Neutral = 50% Neutral~Earth = 50% Line~Neutral = 33% Line~Earth = 33% Neutral~Earth = 33% |
|
Surge Counter
Alarms Breakdown Isolation Indication Panel |
Six Digit
Relay Contacts Isolation Voltage LED Indication |
1500A 8/20us Trigger
N.O. 5Amp.240VAC Rated 4KV Power and Surge Diverter Status (On = OK, Off = Fault) |
|
International Standards | Surge Testing | ANSI/IEEE C62.41-1991 AS/NZS 1768-1991 | |
Abnormal Overvoltage Testing | SDM_-xxxK-M-RR/T
(T-version only) |
UL1449 ed.2 | |
Physical
Enclosure Mounting Cable Termination |
Temperature Range
Environmental rating Metal Enclosure Finish Colour Heat Loss Rear screw under cover Screw & Bolt Connection Cable Entrance |
-10 to 80 °C, 0~90% humidity
Ip66 Dip Coat Primed & Powder Coated RAL 7032 < 30 watts 4×8 Æ bolt or external feet option Flexible cable Bottom gland plate |
|
Model Weight SDM-140K-M-RR-SCD 7 kg | Terminals Copper Lug 6mm Æ Screw | Dimensions (Height x Width x Depth) 250mm x 200mm x 150mm |